TECHNICAL DATA & SERVICE MANUAL Outdoor Unit Indoor Unit 4-Way Air Discharge Semi-Concealed Wall-Mounted Ceiling-Mounted Concealed-Duct Concealed-Duct High-Static Pressure SPW-C706VH8, SPW-C906VH8 Indoor Unit Class SPW- SPW- SPW- SPW- X 4-Way Air Discharge XDR184GH56(A/B) XDR254GH56(A/B) XDR364GH56(A/B) XDR484GH56(A/B) Semi-Concealed X185H X255H X365H X485H 4-Way Air Discharge SPW-...
1. SPECIFICATIONS 1-1. Unit Specifications....................1-2 4-Way Air Discharge Semi-Concealed Type ..................1-2 Wall-Mounted Type ..........................1-13 Ceiling-Mounted Type ........................... 1-16 Concealed-Duct Type ..........................1-26 1-2. Major Component Specifications ................1-49 (A) Indoor Units ............................. 1-49 (B) Outdoor Units ..........................1-67 1-3.
1-3. Other Component Specifi cations 4-Way Air Discharge Semi-Concealed Type SPW-XDR184-484GH56 (A/B), X185-485H SPW-XDR184-484GH56 (A/B) MODEL No. Indoor Unit SPW-X185-485H Power Transformer – Rated – Source VAC, Hz – – Secondary – Ω Coil resistance – Thermal cut off temperature °C –...
Page 75
1-3. Other Component Specifi cations 4-Way Air Discharge Semi-Concealed Type SPW-XM185H MODEL No. Indoor Unit SPW-XM185H Power Transformer – Rated – Source VAC, Hz – – Secondary – Ω Coil resistance – Thermal cut off temperature °C – Thermistor (Coil sensor): TH PB2M-41E-S15-1 kΩ...
1-3. Other Component Specifi cations Concealed-Duct Type SPW-UR184-484GH56 (A/B), UR184-484SH56B, U185-485H, U185-485SHT SPW-UR184-484GH56 (A/B) SPW-UR184-484SH56B MODEL No. Indoor Unit SPW-U185-485H SPW-U185-485SHT Power Transformer ATR-IL225B-T-R Rated Source VAC, Hz AC 230 V, 50 Hz S1: DC 13.0 V, 1 A Secondary S2: DC 24.0 V, 0.2 A Ω...
Page 79
1-3. Other Component Specifi cations Concealed-Duct Type SPW-US185H MODEL No. Indoor Unit SPW-US185H Power Transformer – Rated – Source VAC, Hz – – Secondary – Ω Coil resistance – Thermal cut off temperature °C – Thermistor (Coil sensor): TH PB2M-41E-SI5-1 E1,E2 kΩ...
Page 80
1-3. Other Component Specifi cations Outdoor Units SPW-C706VH8 MODEL No. Outdoor Unit SPW-C706VH8 Power Transformer – Rated – Source VAC, Hz – – Secondary – Ω Coil resistance – Thermal cut off temperature °C – Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4 KTM-35D-S1, DTN-C532G3H kΩ...
Page 81
1-3. Other Component Specifi cations Outdoor Units SPW-C906VH8 MODEL No. Outdoor Unit SPW-C906VH8 Power Transformer – Rated – Source VAC, Hz – – Secondary – Ω Coil resistance – Thermal cut off temperature °C – Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4 KTM-35D-S1, DTN-C532G3H kΩ...
1-4. Dimensional Data (A) Indoor Units: 4-Way Air Discharge Semi-Concealed (X) Type 18, 25 Types 860 – 910 Ceiling opening dimensions Suspension bolt pitch 1-77...
Page 83
1-4. Dimensional Data (A) Indoor Units: 4-Way Air Discharge Semi-Concealed (X) Type 36, 48 Types 1-78...
Page 84
1-4. Dimensional Data (A) Indoor Units: 4-Way Air Discharge Semi-Concealed (XM) Type 18 Type 1-79...
Page 85
1-4. Dimensional Data (A) Indoor Units: Wall-Mounted Type 18 Type 7, 9, 12, 18 type Drain and wiring port (ø9.52) Gas tube ø12.7 (length: Approx. 400 mm) LIquid tube ø6.35 (length: Approx. 470 mm) Drain hose VP13 (length: Approx. 450 mm) 25 type 25 Type 1,140...
Page 86
1-4. Dimensional Data (A) Indoor Units: Ceiling-Mounted Type Length Type Air intake 1125 1180 36, 48 1540 1595 Ceiling side 27.5 27.5 Unit: mm (Suspension bolt pitch) Rear (Figure shows view from front) Left side Right side (Liquid tubing • Gas tubing) Liquid tubing...
Page 87
1-4. Dimensional Data (A) Indoor Unit: Concealed-Duct (U) Type 18 Type SPW-UR184GH56 (A/B), U185H (Air outlet duct flange) (Suspension bolt pitch) Refrigerant liquid line ø6.35 (liquid tube) Refrigerant gas line ø12.7 Upper drain port (O.D. 32 mm) Bottom drain port (O.D. 32 mm) Suspension lug Power supply outlet (2-ø30) Fresh air intake port (ø150)
Page 88
1-4. Dimensional Data (A) Indoor Unit: Concealed-Duct (U) Type SPW-UR254GH56 (A/B), U255H Indoor unit: 25 Type (Air outlet duct flange) (Suspension bolt pitch) Refrigerant liquid line ø9.52 (liquid tube) (Use the tube connector) Refrigerant gas line ø15.88 (gas tube) Upper drain port (O.D. 32 mm) Bottom drain port (O.D.
Page 89
1-4. Dimensional Data (A) Indoor Unit: Concealed-Duct (U) Type SPW-UR364GH56 (A/B), U365H SPW-UR484GH56 (A/B), U485H Indoor unit: 36, 48 Type (Air outlet duct flange) (Suspension bolt pitch) Refrigerant liquid line ø9.52 (liquid tube) Refrigerant gas line ø15.88 (gas tube) Upper drain port (O.D. 32 mm) Bottom drain port (O.D.
1-7. Capacity Correction Graph According to Temperature Condition SPW-C706 / 906VH8 Max. Capacity & Input Change Characteristics When the Outdoor Air Temperature Changes : Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) For 50 Hz and 60 Hz For 50 Hz and 60 Hz Indoor air intake temp (WB) Indoor air intake temp (°C DB)
1-8. Noise Criterion Curves Wall-Mounted Type Both 50Hz / 60Hz Strong Weak MODEL SPW-KR254GH56 (A/B) MODEL SPW-KR184GH56 (A/B) SOUND LEVEL : STRONG 38 dB(A) SOUND LEVEL : STRONG 41 dB(A) MEDIUM 34 dB(A) 37 dB(A) MEDIUM WEAK 30 dB(A) WEAK 34 dB(A) 1 m in front at height of 1 m CONDITION...
1-8. Noise Criterion Curves Ceiling-Mounted Type Both 50Hz / 60Hz Strong Weak SPW-TDR184GH56 (A/B) MODEL MODEL SPW-TDR254GH56 (A/B) SPW-T185H SPW-T255H STRONG SOUND LEVEL : STRONG 36 dB(A) SOUND LEVEL : 38 dB(A) WEAK 30 dB(A) WEAK 33 dB(A) CONDITION CONDITION 1 m from front of outlet at height of 1 m 1 m from front of outlet at height of 1 m NC-50...
1-8. Noise Criterion Curves Cooling (B) Outdoor Unit Heating MODEL SPW-C706VH8 MODEL : SPW-C706VH8 SOUND LEVEL 57 dB(A) COOLING SOUND 71 dB(A) POWER LEVEL HEATING 57 dB(A) Cooling 1 m in front at height of 1.5 m CONDITION NC-70 NC-70 NC-60 NC-60 NC-50...
1-9. Indoor Fan Performance Booster Cable for Concealed-Duct Type Electrical component box If external static pressure is too great (due to long Booster cable extension of ducts, for example), the airflow volume Booster cable motor may drop too low at each air outlet. This problem may be solved by increasing the fan speed using the Fan motor socket following procedure:...
Page 108
For Short Circuit Connection The standard (before shipment) external static pressure is shown in the table below. When using with a higher static pressure, it is necessary to change to the high static pressure mode. White Yellow Red External static pressure Standard High static pressure TP6 TP3 TP1...
1-10. Airfl ow Distance Chart 4-Way Air Discharge Semi-Concealed Type If an ultra long-life fi lter or high performance fi lter (65% by colorimetric method) is installed, the vertical air fl ow distance for heating and cooling will be approximately 0.2 m less than the values shown in the graph below. If a high performance fi...
Page 110
SPW-XDR254GH56(A/B), X255H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.65 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.65 ) (Room temperature approx.20 Horizontal air flow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.30 )
Page 111
SPW-XDR364GH56(A/B), X365H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.65 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.65 ) (Room temperature approx.20 Horizontal air flow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.30 )
Page 112
SPW-XDR484GH56(A/B), X485H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.65 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.65 ) (Room temperature approx.20 Horizontal air flow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.30 )
Page 113
SPW-XM185H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.60 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.60 ) (Room temperature approx.20 Horizontal air flow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.30 )
Page 114
Wall-Mounted Type SPW-KR184GH56(A/B) Heating : Distribution of wind velocity Heating : Distribution of temperature (Strong wind : (Strong wind : Discharge angle app.60 ) (Rm. temp. app.20 Discharge angle app.60 ) (Rm. temp. app.20 1.5m/s 1.2m/s 0.9m/s 0.3m/s 0.6m/s 0.3m/s Horizontal air flow distance (m) Horizontal air flow distance (m) Cooling : Distribution of wind velocity...
Page 115
Ceiling-Mounted Type SPW-TDR184GH56(A/B), T185H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 Horizontal air flow distance (m) Cooling : Distribution of wind velocity...
Page 116
SPW-TDR254/364GH56(A/B), T255/365H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 Horizontal air flow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.
Page 117
SPW-TDR484GH56(A/B), T485H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 Horizontal air flow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.
1-11. Intaking Fresh Air of Semi-Concealed Type and Concealed-Duct Type Precautions Regarding External Air Intake (1) Ventilation Load Ensure that the design of the air-conditioner takes air-conditioning loads into consideration when external air intake is involved. (2) Restrictions on External Air Intake Ensure that the design conforms to the restrictions on air intake volume stipulated in accordance with the model of the indoor unit and the intake method.
Page 119
X, XM Type When an External Air Intake Flange (ø100) is in Use External Air Intake Volume and Resistance and With the External Air Intake Flange Attached Operation Noise Characteristics within the Unit X Type XM Type Duct (ø100) for Connecting the External Air Intake Flange Operation Noise (External Air Intake Only)
1-12. Installation Instructions Tubing Length (A) Single type During tubing work, try to make both the tubing length (L) Single and the difference in elevation (H1) as short as possible. Refer to Table 1-1. Main tubing L Table 1-1 Tubing Data for Models (Single) Models SPW-C706VH8 SPW-C906VH8...
Page 121
(B) Simultaneous operation multi (Twin, Triple, Double-Twin) NO T E Because the indoor units run simultaneously, install them within the same room Table 1-2 Table for Managing Tubing Length and Height Differential Actual Symbol Item Contents length Single Twin Triple Double-Twi n (m ) Maximum...
Page 122
Table 1-3 Connection Tube Sizes (Twin, Triple, Double-Twin) Double-Twin distribution tube (L1, L2) Indoor unit connection tube Main tubing (L) Total type capacity of indoor unit connected after ( 1, 2, 3, 4) the branch Type capacity of indoor unit 36 –...
Page 123
This unit requires no additional refrigerant CAUTION charge up to tubing length 30 m. In case of more than 30 m, additional refrigerant charge is required. Refer to Tables 1-1 and 1-3. In case of multi type installation, indoor units should be installed within the same room.
Optional Distribution Joint Kits APR-P160BG: Cooling capacity after distribution is 16.0 kW (54,600 BTU/h) or less. APR-P680BG: Cooling capacity after distribution is more than 16.0 kW (54,600 BTU/h) and less than 68.0 kW (232,000 BTU/h). APR-RTP280AGB: Cooling capacity after distribution is 28.0 kW (95,500 BTU/h) or less. Table 1-5 Distribution Branch Size ( 1, 2, 3, 4) Unit: mm (in.)
Page 125
Installing Distribution Joint Kit (for Twin & Double-Twin) (APR-P160BG & APR-P680BG) Horizontal Installation For branching tubes, install 150 mm or longer (including reducer) straight tubing up to the point Horizontal line where the tube branches (or after the point where Indoor unit side the tubes join together).
Installing Distribution Joint Kit (for Triple) (APR-RTP280AGB) Check the system combination before installing the distribution joints. Three indoor units must be installed within the same room. Use the supplied tube connectors to adjust the tube sizes of the distribution joints. How to Install Distribution Joints Distribution joint insulation material (supplied) Use the supplied distribution joints to complete refrigerant...
SELECTING THE INSTALLATION SITE CAUTION Ceiling-Mounted Type When moving the unit during or after unpacking, Ceiling make sure to lift it by holding its lifting lugs. Do not exert any pressure on other parts, especially the refrigerant piping, drain piping and flange parts. If you think the humidity inside the ceiling might Wall exceed 30...
Page 128
Installation space Air intake Install the outdoor unit with a sufficient space around the Air intake outdoor unit for operation and maintenance. (1) Obstructions on the left side, right side and rear side (Front side and above the unit are opened). (Fig. 1-7) Air discharge Air discharge Anchor bolts...
Page 129
Precautions for Installation in Heavy Snow Areas (1) The platform should be higher than the max. snow depth. (Fig. 1-12) (2) The 2 anchoring feet of the outdoor unit should be used for the platform, and the platform should be installed beneath the air intake side of outdoor unit.
Page 130
Dimensions of Air-Discharge Chamber : STK-UFV160E In snowy regions, if there is concern that snow may enter the air discharge chamber, remove the base of the chamber before using. Unit: mm Reference diagram for SPW-C706 / 906VH8 Air discharge support (STK-FV140B) Air intake Downward, Left side installation fixture (STK-UFV80E)
Page 131
Reference diagram for downward left side installation fixture (field supply) : STK-UFV80E Unit: mm 2-o3.3 protrusion hole (reverse side) Reference diagram for downward right side installation fixture (field supply) : STK-UFV80E Unit: mm 2-o3.3 protrusion hole (reverse side) Cyclic bending 1-126...
Page 132
Reference diagram for downward center side installation fixture (field supply) : STK-UFV80E Unit: mm Cyclic bending 32.5 (495) 32.5 Same on reverse side (135) 1-127...
Page 133
Reference diagram for upward left side installation fixture (field supply) : STK-UFV160E Unit: mm 10.5 145.5 Reference diagram for upward right side installation fixture (field supply) : STK-UFV160E Unit: mm 10.5 135.5 1-128...
Page 134
Reference diagram for upward left side installation fixture (field supply) : STK-UFV160E Unit: mm 561.5 Reference diagram for upward right side installation fixture (field supply) : STK-UFV160E Unit: mm Cyclic bending 1-129...
Page 135
Reference diagram for air-discharge chamber (fi eld supply) The models of SPW-C706 / 906VH8 with STK-UFV160E Required space around outdoor unit If the air discharge chamber is used, the space shown below must be secured around the outdoor unit. If the unit is used without the required space, a protective device may activate, preventing the unit from operating. (1) Single-unit installation Unit: mm The top and both sides must remain open.
Page 136
Dimensions of Wind-proof Duct : STK-DGV280E In snowy regions, if there is concern that snow may enter the wind-proof duct, remove the base of the chamber before using. Reference diagram for SPW-C706 / 906VH8 Air intake Unit: mm intake discharge Air discharge discharge discharge...
Dimensions of Snow-proof Duct Reference diagram for SPW-C706 / 906VH8 (295) Unit : mm Air intake Air discharge (227) (303) Air discharge Air discharge Air intake Reference diagram for snow-proof duct (field supply) : STK-BDV160E Unit : mm Unit top, snow-proof duct Unit right side Unit left side Unit front side...
Page 138
Reference diagram for snow-proof duct - 1 Space requirements for setting - (1) The models of SPW-C706 / 906VH8 with STK-BDV160E Unit: mm [Obstacle to the rear of unit] [Obstacle to the front of unit] Top is open: Top is open: (1) Single-unit installation (2) Obstacles on both sides (1) Single-unit installation...
Page 139
Reference diagram for snow-proof duct - 2 Space requirements for setting - (2) The models of SPW-C706 / 906VH8 with STK-BDV160E [Obstacles to the front and rear of unit] The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit.
HOW TO INSTALL THE OUTDOOR UNIT Drainage Work Installing the Outdoor Unit Follow the procedure below to ensure adequate draining for Use concrete or a similar material to make the base, the outdoor unit. and ensure good drainage. For the drain port dimensions, refer to Fig. 1-14. Ordinarily, ensure a base height of 5 cm or more.
ELECTRICAL WIRING Control wiring General Precautions on Wiring (C) Inter-unit (D) Remote control (E) Control wiring between outdoor (1) Before wiring, confirm the rated voltage of the unit as and indoor units) wiring for group control shown on its nameplate, then carry out the wiring closely control wiring following the wiring diagram.
Page 142
Wiring System Diagrams (for 3-phase outdoor unit: X, K, T, U and D Types) Indoor unit (No. 1) Power supply Outdoor unit 220 – 240 V, 50/60 Hz* INV unit Ground Power supply 380 – 415 V, 3N, ~ 50/60 Hz Remote controller Ground...
Page 143
(for 3-phase outdoor unit: XM, US Types) Indoor unit (No . 1) Power supply Outdoor unit 220 – 240 V, 50/60 Hz INV unit Ground Po wer supply 380 – 415 V, 3 N, ~ 50/60 Hz Remote controller Ground Ground Ground Indoor...
Page 144
CAUTION (1) When linking the outdoor units in a network (S-net link system), disconnect the terminal extended from the short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) Otherwise the communication of S-net link system is not performed.
Page 145
(5) Use shielded wires for inter-unit control wiring (c) and ground the shield on both sides, otherwise misoperation from noise may occur. (Fig. 1-19) Connect wiring as shown in Section “Wiring System Diagrams”. X, K, T, U, D Types Shielded wire Ground Ground XM, US Types...
2. TEST RUN 2-1. Preparing for Test Run ......................... 2 -2 X, XM, T, U, US, D Types 2-2. Caution..............................2-2 2-3. Test Run Procedure ..........................2-2 2-4. Items to Check Before the Test Run ...................... 2-3 2-5. Test Run Using the Remote Controller ....................2-3 2-6.
X, XM, T, U, US, D Types 2-2. Caution 2-1. Preparing for Test Run This unit may be used in a single-type refrigerant Before attempting to start the air conditioner, system where 1 outdoor unit is connected to 1 check the following: indoor unit, and also in a system where 1 outdoor (1) All loose matter is removed from the cabinet espe- unit is connected to multiple indoor units...
2-6. Precautions 2-4. Items to Check Before the Test Run Request that the customer be present when the test (1) Turn the remote power switch ON at least 12 run is performed. At this time, explain the operation hours in advance in order to energize the crank manual and have the customer perform the actual case heater.
Page 150
2-8. System Control System control refers to the link wiring connection for control of simultaneous-operation multi systems, group control, and mainsub remote controller control. 2-8-1. Basic wiring diagram 1 Single type and simultaneous-operation multi system Simultaneous-operation multi system Up to 4 (Double-Twin) indoor units can be connected to 1 outdoor unit for operation. (However, coordinate the outdoor unit capacity and the total capacity of the indoor units.) (It is not possible to connect individual remote controllers for independent operation.) Be careful to avoid miswiring when connecting the wires.
Page 151
2-8-2. Basic wiring diagram 2 Group control (when a central control device is not used) Simultaneous-operation multi system Up to 4 (Double-Twin) indoor units can be connected to 1 outdoor unit for operation. (However, coordinate the outdoor unit capacity and the total capacity of the indoor units.) (It is not possible to connect individual remote controllers for independent operation.) A maximum of 8 indoor units can be connected to 1 remote controller.
Page 152
(Wiring procedure) (1) Connect the remote controller to the indoor unit re- mote controller wiring terminal plate (1, 2). (Remote controller wiring) (2) Connect the indoor units (U1, U2) and the outdoor units (1, 2). Connect the other outdoor units and indoor units (with different refrigerant systems) in the same way.
Page 153
2-8-4. Automatic address setting using the remote 2-8-3. Setting the outdoor unit system addresses controller For basic wiring diagram 2 (Set the system addresses: When the outdoor unit shown in “2-8-2. Basic wiring 1, 2, 3...) diagram 2” is used for group control of multiple units, 8 –...
K Type 2-8-6. Main-sub remote controller control Control using 2 remote controller switches 2-9. Caution Main-sub remote controller control refers to the use of 2 This unit may be used in a single-type refrigerant remote controllers to control 1 or multiple indoor units. system where 1 outdoor unit is connected to 1 (A maximum of 2 remote controllers can be connected.) indoor unit, and also in a system where 1 outdoor...
2-10. Test Run Procedure 2-12. Preparation for Test Run 2-12-1. Switching the temperature sensor Recheck the items to check (See 2-11) Temperature sensors are contained in the indoor unit before the test run. and wireless remote controller. One or the other of the temperature sensors is used for operation.
2-13. Test Run Indoor unit control PCB Using the control unit 2 HP Varistor (black) (1) Change the indoor control unit switch from VA002 “ON” “TEST”. Fuse (0.5A) (The outdoor unit will not operate for 3 minutes after the power is turned ON and after operation is stop- ped.) CHK (2P plug) (2) All the indicator lamps blink while the test run is in...
2-15. Table of Self-Diagnostic Functions and Corrections (K Type) Cause Wired remote controller Indoor unit Group connection Correction display receiver lamp 1:1 connection (Single type) (Simultaneous multi (Field supply) system) Nothing is Nothing is • Indoor operation switch is OFF. •...
2-16. System Control System control refers to the link wiring connection for control of simultaneous-operation multi systems, group control, and main/sub remote controller control. 2-16-1. Basic wiring diagram 1 Single type and simultaneous-operation multi system Simultaneous-operation multi system Up to 4 (Double-Twin) indoor units can be connected to 1 outdoor unit for operation. (However, coordinate the outdoor unit capacity and the total capacity of the indoor units.) (It is not possible to connect individual remote controllers for independent operation.) Be careful to avoid miswiring when connecting the wires.
Page 159
2-16-2. Basic wiring diagram 2 Group control (when a central control device is not used) A maximum of 8 indoor units can be connected to a single remote controller. Example: In a refrigerant system where 2 or 3 indoor units are connected to 1 outdoor unit, set the new system address (refrigerant system address) before turning ON the remote power switch.
Page 160
2-16-3. Setting the outdoor unit system addresses 2-16-4. Automatic address setting from the outdoor unit For basic wiring diagram 2 (Set the system addresses: When there are multiple outdoor units as shown in basic 1, 2,...) wiring diagram 2 Outdoor unit control PCB 8 –...
X, T, U, D Types (for Link Wiring) 2-16-6. Indoor unit address setting 2-17. Caution If multiple single-type units are installed in the same room the addresses can be set to prevent signal inter- This unit may be used in a single-type refrigerant ference.
2-18. Test Run Procedure 2-19. Items to Check Before the Test Run (1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crank case Recheck the items to check (See 2-19) before the test run. heater.
2-21. Table of Self-Diagnostic Functions and Corrections (X, T, U, D Types) Cause Wired remote Indoor unit controller Correction Group connection and simultaneous-operation multi receiver lamp display system • Remote controller is not connected with indoor unit Connect the remote controller correctly. Turn ON the Nothing is Nothing is correctly.
2-22. Automatic Address Setting 2-22-1. Basic wiring diagram Link wiring NO T E A terminal plug (black) is attached to each of the outdoor unit control PCBs. At only one outdoor unit, leave the terminal plug short-circuit socket on the “Yes” side. At all the other outdoor units, change the socket (from “Yes”...
Page 165
Automatic address setting using the remote cont- 2-22-2. Setting outdoor unit system addresses roller For the basic wiring diagram (Set the system addresses: Case 3 1, 2, 3...) If the power can be turned ON separately for the Outdoor unit control PCB 8 –...
2-22-3. Checking indoor unit addresses Check that the 220 – 240 V AC wiring is not connected Use the remote controller to check the addresses of the to the inter-unit control wiring connector terminal. indoor units. Press and hold the button and If 220 –...
2-24. Test Run Procedure Recheck the items to check (See 2-11) before the test run. Check the combination (wiring) of (See 2-26-1) indoor and outdoor units. Is system “single-type”? (1 indoor unit is connected to 1 outdoor unit) Turn ON Are multiple outdoor units the indoor used?
2-25. Table of Self-Diagnostic Functions and Corrections (K Type) Cause Wired remote Indoor unit controller Correction Group connection and simultaneous-operation multi receiver lamp display system • Remote controller is not connected with indoor unit Connect the remote controller correctly. Turn ON the Nothing is Nothing is correctly.
2-26. Automatic Address Setting 2-26-1. Basic wiring diagram Link wiring NO T E A terminal plug (black) is attached to each of the outdoor unit control PCBs. At only 1 outdoor unit, leave the terminal plug short-circuit socket on the “Yes” side. At all the other outdoor units, change the socket (from “Yes”...
Page 170
2-26-2. Setting the outdoor unit system addresses System address System address System address 10s digit 1s place For basic wiring diagram (Set the system addresses: (2P DIP switch) (Rotary switch) 1, 2, 3...) Both OFF “0” setting Outdoor unit control PCB 8 –...
Page 171
2-26-3. Checking indoor unit addresses Automatic address setting from the outdoor unit (K type) Use the remote controller to check the addresses of the indoor units. Press and hold the button and butt- (1) Turn on the indoor and outdoor unit power for on for 4 seconds or longer (simple settings mode, “ALL”...
XM Type (for Link Wiring) 2-28. Test Run Procedure 2-27. Caution This unit may be used in a single-type refrigerant Recheck the items to check system where 1 outdoor unit is connected to 1 in- (See 2-29) before the test run. door unit, and also in a system where 1 outdoor unit is connected to multiple indoor units (maximum 4 <...
2-29. Items to Check Before the Test Run (1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crank case heater. (2) Fully open the closed valves on the liquid-tube and gas-tube sides. 2-30.
2-31. Table of Self-Diagnostic Functions and Corrections (XM Type) Cause Wired remote Indoor unit Correction Group connection and simultaneous-operation controller display receiver lamp multi system Remote controller is not connected with indoor Nothing is Connect the remote controller correctly. Nothing is displayed unit correctly.
2-32. Automatic Address Setting 2-32-1. Basic wiring diagram Link wiring NOTE A terminal plug (black) is attached to each of the outdoor unit control PCBs. At only one outdoor unit, leave the terminal plug short-circuit socket on the “Yes” side. At all the other outdoor units, change the socket (from “Yes”...
Page 176
Automatic address setting using the remote cont- 2-32-2. Setting outdoor unit system addresses roller For the basic wiring diagram (Set the system addresses: 1, 2, 3...) Case 3 If the power can be turned ON separately for the Outdoor unit control PCB indoor and outdoor units in each system (indoor unit System address rotary switch addresses can be set without running the compressor):...
2-32-3. Checking indoor unit addresses Installing the batteries Use the remote controller to check the addresses of the (1) Press on both sides of the remote controller cover indoor units. Press and hold the button and and slide it downward to remove it. button for 4 seconds or longer (simple settings mode, “ALL”...
Page 178
Caution on Pump Down (Refrigerant Recovery) NO T E Pump down cannot be performed when the tubing length exceeds 30m. (There is a possiblilty of generating the actuation of the excessive load protection system.) In this case, collect the refrigerant by the refrigeant collecting system.
3. ELECTRICAL DATA 3-1. Indoor Units (Electric Wiring Diagram, Schematic Diagram) ......... 3-2 4-Way Air Discharge Semi-Concealed Type ................... 3-2 Wall-Mounted Type ..........................3-5 Ceiling-Mounted Type ..........................3-9 Concealed-Duct Type ..........................3-11 Concealed-Duct High-Static Pressure Type .................... 3-19 3-2. Outdoor Units (Electric Wiring Diagram, Schematic Diagram) ......3-23...
4. PROCESS AND FUNCTIONS 4-1. Control Functions ....................... 4-2 4-2. Outdoor Unit Control PCB ..................4-8 4-3. Indoor Unit Control PCB Switches and Functions ..........4-11...
4-1. Control Functions 1. Indoor Air Temprature Control The thermostat is switched on and off in accordance with T shown below. = (Indoor air temperature) - (Temperature set with the remote controller) In the body thermostat mode Indoor air temperature = (Body sensor) - (Shift temperature *) (setting at factory shipment) In the remote controller thermostat mode Indoor air temperature = (Remote controller sensor)
Page 206
2) Maximum and Minimum Frequency Control The compressor's inverter frequency is controlled in accordance with the model and operation mode. The maximum and minimum frequencies for each model are shown in the chart below. There are cases in which frequency is limited with other control functions depending on operational conditions, so operations are not always carried out in accordance with the maximum frequencies listed below.
Page 207
5) Heating High-Load Prevention Control The following control is performed in the heating mode in accordance with the indoor heat exchanger temperature max (E1, E2). (See the chart below.) The operational frequency of the compressor is decreased when the temperature enters the "M" zone. The operation frequency is modified every 30 seconds while the temperature remains in this zone (the thermostat is switched off if it continues for 2 minutes).
Page 208
7) Discharge Temperature Control The following control is performed to prevent the discharge temperature from rising abnormally in order to protect the inverter compressor. In accordance with the temperature of the discharge sensor TD, such controls are performed as to limiting the increase of inverter frequency, decreasing it or halting operation of the compressor.
Page 209
Heating Mask Time This refers to the shortest time that heating operations must be performed without defrosting operations being executed. The mask time for this model is 25 minutes. Defrosting operations will not be commenced until the defrosting mask time has elapsed, even if frost adherence has been detected.
Page 210
12) Demand Control There are two styles of demand operations available as methods of restraining power consumption. (1) Demand via External Input Demand input from an external source is carried out from the outdoor unit EXCT (CN030) PCB or the outdoor unit's serial/parallel I/O (optional).
4-2. Outdoor Unit Control PCB (1) Layout Diagram (CR-C906VH8) Fuse (F101) RC_P (CN039) EXCT (CN030) SILENT (CN037) PUMP DOWN (CN048) A.ADD (CN047) Sensor at upper side of heat exchanger (C2) Sensor at lower side of heat exchanger (C1) Suction temp. (TS) Outdoor air temp.
Page 212
4-2. Outdoor Unit Control PCB (CR-C906VH8) (2) Explanation of Functions Auto Address Pin 2P (white): Automatic address setting switch (CN047) If the system address switch (S002: set to 0 at time of shipment) setting is other than “0” (central control), press this switch once to automatically set the addresses at all indoor units which are in the same system, and are connected to that outdoor unit.
Page 213
Quiet mode plug 2P plug (white): Enables operation in quiet mode. (CN037) The outdoor unit fan and compressor frequencies are subject to limits during operation. Low-noise operation is enabled when the relay is turned ON. (Non-voltage contact "a" ) Example of wiring Relay (field supply) Power Quiet mode External contact...
4-3. Indoor Unit Control PCB Switches and Functions [Indoor unit control PCB] T10 (CN61): 6P plug (YEL) / Used for remote control operation. (Refer to the Remote Control Section.) Control items: (1) Start/stop input (2) Remote controller prohibit input (3) Start signal output (4) Alarm signal output EXCT (CN73): 2P plug (RED) / Can be used for demand control.
Page 215
4-3. Indoor Unit Control PCB Switches and Functions For AC Fan Motor (CR-UXRP71B-B) EEPROM (IC010) OC (CN040) EMG (CN044) VARISTOR (VA100) JP001 OPTION (CN060) EXCT (CN073) GRL (CN020) DISP (CN072) POWER LED (D002) CHK (CN071) FAN DRIVE (CN032) T10 (CN061) FILTER (CN070) For DC Fan Motor (CR-SXRP56B-B) POWER LED (D002)
Page 216
For DC Fan Motor (CR-KRP50A) OPTION (CN014) FAN DRIVE (CN017) T10 (CN015) DISP (CN010) CHK (CN011) VARISTOR (VA002) JP001 EMG (CN018) EEPROM (IC002) EXCT (CN009) OC (CN019) FILTER (CN012) For DC Fan Motor (CR-KRP80A) OC (CN019) EEPROM (IC002) JP001 EMG (CN018) VARISTOR (VA002) CHK (CN011) DISP (CN010)
5. SERVICE PROCEDURES 5-1. Meaning of Alarm Messages ..................5-2 5-2. Contents of LED Display on the Outdoor Unit Control PCB ........5-4 5-3. Symptoms and Parts to Inspect ................5-5 5-4. Details of Alarm Messages ..................5-8 5-5. Table of Thermistor Characteristics ................. 5-14 5-6.
5-1. Meaning of Alarm Messages 1. Contents of the alarm display on the remote controller Blinking: OFF: Wireless remote controller Lamp display Display Possible cause of malfunction Remote controller is Error in receiving serial communication signal Serial commu- detecting error signal from (Signal from main indoor unit in case of group control) nication errors indoor unit...
Page 220
Blinking: OFF: Wireless remote controller Lamp display Display Possible cause of malfunction Ceiling panel connection failure Indoor protection Activation of Fan protective thermostat protective Alter. Float switch device DC fan error. Discharge temperature trouble Outdoor protection Open phase detected, AC power trouble No gas 4-way valve locked High cooling load...
5-2. Contents of LED Display on the Outdoor Unit Control PCB LED 1 LED 2 Remarks Power ON sequence 1. No communication from indoor units in system If it is not possible to advance to 3, repeats 1 2. Communication received from 1 or more indoor units in system At 3, changes to normal 3.
5-3. Symptoms and Parts to Inspect Remote Alarm Eliminating controller Judgement conditions Judgement and correction contents condition of alarm alarm display Stops when temp. exceeds Recovery at restart 1. Check refrigerant cycle (gas Abnormal discharge temperature error. leak). Discharge temp. Alarm output on 4 pre-trips.
Page 223
Remote Alarm Eliminating Judgement and correction controller Judgement conditions contents condition of alarm alarm display Error in current Inverter halted after alarm Recovery at restart 1. Stops immediately even when detection circuit. detected. operations restarted. AC current value is Layer short on the Alarm output on 4 high, even while consecutive (pre-trips.)
Page 224
Remote Alarm Eliminating Judgement and correction controller Judgement conditions contents condition of alarm alarm display Settings failure Main unit in simultaneous Power reset 1. Check inter-unit control operation multi control recovery wiring. 2. Check indoor unit duplicated. (Outdoor unit detected) combination.
5-4. Details of Alarm Messages Alarm Details (1) [Alarm “P29”] Start-up failure of the compressor (will not start up) Related parts HIC PCB (Model: [706-type, 906-type] HIC-C1155GDXH8) Outdoor unit control PCB (Model: [706-type, 906-type] CR-C906VH8) Start of defect diagnosis Filter PCB (Model: [706-type, 906-type] FIL-C906VH8) Is the power Improve the power voltage line.
Page 226
(2) [Alarm P26] Start-up failure of the compressor (will not start up) Related parts HIC PCB (Model: [706-type, 906-type] HIC-C1155GDXH8) Outdoor unit control PCB (Model: [706-type, 906-type] CR-C906VH8) Start of defect diagnosis Filter PCB (Model: [706-type, 906-type] FIL-C906VH8) Was everything OK when in the diagnosis Implement the same check processes for...
Page 227
HIC-C1155GDXH8 (706, 906 Types) HIC + Resistance Between terminals Resistance 200 k or more HIC + HIC – 300 k or more HIC + 300 k or more HIC + 300 k or more HIC + 200 k or more HIC –...
Page 228
(4) [Alarm "P22"] Outdoor unit fan motor drive circuit trouble Start of defect diagnosis Are the connectors CN003, CN005, Correct the connections CN041 and CN042 connected correctly to the outdoor unit control PCB? Does the fan rotate without resistance when spun manually after the connectors Fan motor trouble Replace CN003, CN005, CN041 and CN042 are...
Page 229
Sensor trouble (5) [Alarms “F04,” “F06,” “F07,” “F08,” “F12”] Start of defect diagnosis Are the connectors of the sensor 020 (C2), 021 (C1), 022 (TS), Correct the connections. 023 (TO) and 024 (TD) connected correctly to the outdoor unit control PCB ? Are the characteristics of resistance values of the Replace the sensors C2, C1, TS, TO and TD.
Page 230
Sensor Temperature Display Function (Displayed regardless of operation and stop) The below check procedure can be used to display all remote controller, indoor unit, and outdoor unit sensor temperatures. <Check procedure> (1) Press and hold the button and button simultaneously for 4 seconds or longer.
5-6. How to Remove the Compressor Pay careful attention to prevent water or foreign objects from entering into the refrigerant tubing when removing or installing the compressor. Removing 1. After collecting the refrigerant in the system, replace nitrogen gas from the service port of the gas tubing valve. 2.
5-7. How to Remove the Electrical Component Box Removing 1. Remove the front panel and inspection panel from the outdoor unit. 2. Remove all local wires connected to the electrical component box. 3. Remove the wires (temperature sensor, coils of every sort of valve, pressure switch, fan motor and wires for connecting compressor) connected to the electrical component box in the unit.
6. OUTDOOR UNIT MAINTENANCE REMOTE CONTROL 6-1. Overview ........................6-2 6-2. Functions ........................6-2 6-3. Normal Display Operations and Functions ............... 6-3 6-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures ....................... 6-6 6-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History ..........................
6-1. Overview What is the outdoor unit maintenance remote controller? Beginning with the DC-INV series of outdoor units, nonvolatile memory (EEPROM) is used in the outdoor unit PCB. In this way, the setting switches that were located on earlier PCBs have been converted to EEPROM data. This remote controller is an outdoor unit maintenance tool that is used to make and change the EEPROM set- tings.
6-3. Normal Display Operations and Functions Normal display functions Connect the special service checker wiring to the outdoor unit PCB. The connection is shown in the figure below. Interface for outdoor unit maintenance Outdoor unit remote controller (ACC-CR-RCS) control PCB RC (5P, red) Relay connector (2P, white) Special service checker wiring...
Page 237
Display (functions) • Use the temperature setting buttons to change the item code. 00 (1) Blinking 8-alarm code display at pre-trip, LED (2) No. of indoor units connected in that refrigerant system Unit. Nos. of connected indoor units in that refrigerant system *2 Operating status of indoor units in that refrigerant system (blinks when alarms occur) *2 Unit Nos.
Page 238
*2: 7-segment, 4-digit display for remote controller timer display The connected unit Nos. are displayed as shown below, using the 7-segment 4-digit ( ) display and the colon. ● Display for unit Nos. 1 – 20 Not lit Not lit Not lit Not lit Meaning of display colon...
6-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures <Operating procedure> (1) Press and hold the button and button simultaneously for 4 seconds or longer to switch to temperature monitor mode. During temperature monitoring, “Service Monitor” is lit. (The display and operations are the same as when monitor mode is started from the unit remote controller.) (2) Press...
6-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History Displays outdoor unit alarms only. Does not display indoor unit alarms. Check the indoor unit alarm histories separately using the indoor unit remote controllers or other control device. <Operating procedure>...
Page 241
List of Item Codes (Some item codes cannot be set due to the type of models.) Item code Parameter Control system schedule Do not set Control system schedule Do not set Control system schedule Do not set Snowfall sensor operation 0 = No sensor, control performed 1 = No sensor, control not performed 2 = Sensor present, control performed...
Page 242
Setting mode 2 <Operating procedure> (1) Press and hold the button, button, and button simultaneously for 4 seconds or longer. (2) Use the temperature setting buttons to change the item code. The item codes and setting data are shown in the table below. (3) Use the timer time buttons to change the setting data.
7-1. Simple Settings Function • This allows the filter lifetime, operating mode priority change, central control address, and other settings to be made for an individual or group- control indoor unit to which the remote controller used for simple settings is connected. When simple settings mode is engaged, operation stops at the individual or group-control indoor unit to which the remote controller for simple settings is...
7-2. List of Simple Setting Items Setting data Item code Item Description 0000 Not displayed 0001 150 hours Filter sign ON time 0002 2,500 hours (filter life time) 0003 5,000 hours 0004 10,000 hours 0005 Use the filter clogging sensor. 0000 Standard (setting at time of shipping) Degree of filter fouling Highly fouled...
7-3. Detailed Settings Function • This allows the system address, indoor unit address, and other settings to be made for the individual or group-control indoor unit to which the remote controller used for detailed settings is connected. When detailed settings mode is engaged, operation stops at the individual or group-control indoor unit where the remote controller used for detailed settings is connected.
7-4. List of Detailed Setting Items Setting data Item Item code Description Description Description 4-Way Air Discharge 1-Way Air Discharge 2-Way Air Discharge Semi-Concealed 0000 0001 0002 Semi-Concealed (A) Semi-Concealed (S) (X, XM) Concealed-Duct Concealed-Duct High 1-Way Air Discharge 0003 0005 0006 Type...
Page 249
Setting data Item code Item Description Forced thermostat ON 0000 5 minutes (1B) time 0001 4 minutes –10°C –010 –9°C –009 Cooling discharge –8°C –008 temperature shift 0010 10°C –10°C –010 –9°C –009 Heating discharge –8°C –008 temperature shift 0010 10°C 0001 ±...
Page 250
Setting data Item code Item Description 0000 No forced operation 0001 Forced operation for 1 minute Automatic drain pump operation Continuous operation 0060 None 0000 Ventilation fan operation 0001 Ventilation fan operated by remote controller. Wired remote controller 0000 Not used. (Body sensor is used.) Remote control sensor is used.
Page 251
Setting data Item code Item Description DC fan tap Purpose operating mode 0000 Standard Standard (setting at shipment) High ceiling use High ceiling setting 1 (with standard panel) Ultra long-life filter, oil guard panel, ammonia 0001 For low static- deodorizing filter, optical regenerative pressure filter Fan tap setting deodorizing filter...
7-5. Simple Setting Items Item code Item Description Filter sign ON time setting Changes the indoor unit filter lifetime when a high-performance filter or (filter lifetime) other optional product is installed. Reduces the filter sign ON time to 1/2 of the standard time (setting at the Degree of filter fouling time of shipping) for cases when filter fouling is more severe than normal.
Page 253
Item code Item Description Set when using a central control device. Central control address Used when setting the central control address manually from the remote controller. Operating mode priority change Note (1) NOTE (1) Explanation of operation mode priority change Enabled only in 2WAY MULTI heat-pump models.
Page 254
When the operating mode at the priority remote controller is changed, the operating modes of other remote controllers change as shown below. Mode change at priority remote controller Operating modes at other remote controllers Current mode New mode Current mode New mode Cooling or dry Heating...
7-6. Detaild Setting Items Item code Item Description Unit type Set when the indoor unit EEPROM memory is replaced during servicing. Indoor unit capacity System (outdoor unit) These are not set at the time of shipping from the factory. address These must be set after installation if automatic address setting is not Indoor unit address performed.
Page 256
Item code Item Description 1F (Upper limit) Cooling 20 (Lower limit) This setting changes the temperature range (upper limit and lower 21 (Upper limit) Change to the Heating limit) which is set from the remote controller or central control device. 22 (Lower limit) remote control The set upper limit must be greater than or equal to the lower limit.
Page 257
(Continued from previous page) Item code Item Description Heat exchanger The heat exchanger temperature control point for prevention of cold temperature for cold air air discharge during heating operation can be changed. discharge The indoor unit PCB optional output for the fan can be switched Fan output switching according to the purpose of use.
Page 258
DC Fan Tap Change Procedure <Procedure> Be sure to turn the main power OFF before performing the steps below. (1) Check the optional product that will be used from the table below. Setting No. Optional part name Optional part No. Super long-life filter AFT-LS140A Oil guard panel...
7-7. Remote Controller Servicing Functions • The remote controller includes a number of servicing functions. Use these as needed for test runs and inspections. List of Servicing Functions Functions Description Button operation Reset operation Unit status Operation with forced Press and hold the button for 4 Test run thermostat ON...
Page 260
Sensor Temperature Display Function (displayed regardless of whether unit is operating or stopped) The procedure below displays the sensor temperatures from the remote controller, indoor unit, and outdoor unit on the remote controller. <Procedure> 1 Press and hold the buttons simultaneously for 4 seconds or longer.
8. HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER RECEIVER ■ Warning 8-1. Warning about Installation of Receivers ..............8-2 8-2. Warning about Installing Remote Controls .............. 8-2 ■ RCS-SH80BG.WL for 4-Way Cassette (X Type) 8-3. Installing the Receiver Unit ..................8-3 8-4.
■ Warning 8-1. Warning about Installation of Receivers The wireless remote uses a very weak infrared light for its signal, which can result in the signal not being received because of the following influences, so take care in where the unit is installed. ·...
■ RCS-SH80BG.WL for 4-Way Cassette (X Type) 8-3. Installing the Receiver Unit The receiver can only be installed on the corner indicated in Fig. 8-1, so consider how the panel will face when it is installed on the indoor unit. (1) Remove the air inlet grill.
When 1 indoor unit is operated by 2 remote controls: If a group of units are to be controlled by 2 remote controls; Either of the remotes can be set to main/sub. Main/sub remote controls will work regardless of which indoor unit they are installed to.
■ RCS-TRP80BG.WL for Ceiling Mounted (T Type) 8-9. Installing the Receiver Unit (1) Open the air inlet grille on the side panel, remove the 1 screw and then move it toward the front (direction of the arrow) and remove it. (Fig. 8-8) (2) Wrap the tip of a flat head screwdriver with vinyl tape and then slip it into the side of and under where "...
When 1 indoor unit is operated by 2 remote controls: If a group of units are to be controlled by 2 remote controls; Either of the remotes can be set to main/sub. Main/sub remote controls will work regardless of which indoor unit they are installed to.
● When using a receiver that has been installed separately into the ceiling,use the enclosed fittings for installing to a ceiling. (1) Remove the metal plate of the receiver by slipping a flathead screwdriver or the like into the cutout on the bottom. (2) Cut out a hole in the ceiling to match the dimensions of the enclosed template.
8-18. Setting Address Switches ● When more than one receiver and remote control are installed in the same room, setting up addresses allows them to avoid interfering with each other. ● Refer to the Users Manual for information on how to change the addresses of the remote controls. ●...
Page 273
■ Common to All Models 8-20. The Self-Diagnosis Function Display and What is Detected Alarm Display in the table below indicates the content of alarms that are displayed when a wired remote control is connected. For information on how to deal with the alarms, refer to the Mounting Instructions for the indoor unit or to Test Run or servicing materials.
8-22. Setting Up Remote Control Functions The functions of the wireless remote can be set on site. (These settings are saved in nonvolatile memory in the remote control, so even when its batteries are changed, the settings do not revert to the defaults.) NOTE The operation of the air conditioner can be impacted, depending on the settings made, so only service personnel should make the settings.
Page 275