Fujitsu AIRSTAGE ASEH09KLTA Design & Technical Manual
Fujitsu AIRSTAGE ASEH09KLTA Design & Technical Manual

Fujitsu AIRSTAGE ASEH09KLTA Design & Technical Manual

Wall mounted type, indoor/outdoor, refrigerant r32 inverter
Hide thumbs Also See for AIRSTAGE ASEH09KLTA:

Advertisement

Quick Links

AIR CONDITIONER
Wall mounted type
DESIGN & TECHNICAL MANUAL
INDOOR
OUTDOOR
AOEH07KLTA
AOEH09KLTA
AOEH12KLTA
ASEH07KLTA
ASEH09KLTA
ASEH12KLTA
DR_AS221ES_01
2024.01.12

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu AIRSTAGE ASEH09KLTA

  • Page 1 AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASEH07KLTA ASEH09KLTA ASEH12KLTA OUTDOOR AOEH07KLTA AOEH09KLTA AOEH12KLTA DR_AS221ES_01 2024.01.12...
  • Page 2 Mobile” is a trademark of FUJITSU GENERAL LIMITED. ™ Google Play is trademark of Google LLC. ® App Store is a service mark of Apple Inc., registered in the U.S. and other countries. Copyright © 2024 Fujitsu General Limited. All rights reserved.
  • Page 3: Table Of Contents

    CONTENTS Part 1. INDOOR UNIT................1 1. Specifications....................2 2. Dimensions....................4 2-1. Models: ASEH07KLTA, ASEH09KLTA, and ASEH12KLTA ..........4 2-2. Pipe exit length from the rear ...................6 3. Wiring diagrams ....................7 3-1. Models: ASEH07KLTA, ASEH09KLTA, and ASEH12KLTA ..........7 4. Capacity table....................8 4-1. Cooling capacity.......................8 4-2.
  • Page 4 CONTENTS (continued) Part 2. OUTDOOR UNIT..............29 1. Specifications....................30 2. Dimensions....................32 2-1. Models: AOEH07KLTA, AOEH09KLTA, and AOEH12KLTA .........32 3. Installation space ..................33 3-1. Models: AOEH07KLTA, AOEH09KLTA, and AOEH12KLTA .........33 4. Refrigerant circuit ..................36 4-1. Models: AOEH07KLTA, AOEH09KLTA, and AOEH12KLTA .........36 5. Wiring diagrams ..................37 5-1.
  • Page 5: Part 1. Indoor Unit

    Part 1. INDOOR UNIT WALL MOUNTED TYPE: ASEH07KLTA ASEH09KLTA ASEH12KLTA...
  • Page 6: Specifications

    1. Specifications Wall mounted Type Inverter, Heat pump Model name ASEH07KLTA ASEH09KLTA ASEH12KLTA Power supply 230 V~ 50 Hz Power supply intake Outdoor unit Available voltage range 198—264 V Rated Btu/h 6,800 8,500 11,600 Cooling 0.9—2.8 0.9—3.0 0.9—3.7 Min.—Max. Btu/h 3,100—9,600 3,100—10,200 3,100—12,600...
  • Page 7 Wall mounted Type Inverter, Heat pump Model name ASEH07KLTA ASEH09KLTA ASEH12KLTA NOTES: • Specifications are based on the following conditions: – Cooling: Indoor temperature of 27°CDB/19°CWB, and outdoor temperature of 35°CDB/24°CWB. – Heating: Indoor temperature of 20°CDB/15°CWB, and outdoor temperature of 7°CDB/6°CWB. –...
  • Page 8: Dimensions

    2. Dimensions 2-1. Models: ASEH07KLTA, ASEH09KLTA, and ASEH12KLTA Unit: mm 230.6 230.6 Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 317.6 306.6 - 4 - 2-1. Models: ASEH07KLTA, ASEH09KLTA, and ASEH12KLTA 2. Dimensions...
  • Page 9 ¢ Installation space requirement Provide sufficient installation space for product safety. Unit: mm Wall hook bracket 40 or more 30 or more 176 or more 203 or more Outline of the indoor unit 1,500 or more - 5 - 2-1. Models: ASEH07KLTA, ASEH09KLTA, and ASEH12KLTA 2.
  • Page 10: Pipe Exit Length From The Rear

    2-2. Pipe exit length from the rear Design the system considering the length of the pipes or hose exiting from the rear of the indoor unit. NOTE: Detailed shapes of the indoor unit and the tip of each pipe or hose may vary depending on the model.
  • Page 11: Wiring Diagrams

    3. Wiring diagrams 3-1. Models: ASEH07KLTA, ASEH09KLTA, and ASEH12KLTA - 7 - 3-1. Models: ASEH07KLTA, ASEH09KLTA, and ASEH12KLTA 3. Wiring diagrams...
  • Page 12: Capacity Table

    4. Capacity table Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 4-1.
  • Page 13: Heating Capacity

    4-2. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: ASEH07KLTA Indoor temperature °CDB °CWB 1.71 0.79 1.70 0.82 1.67 0.83 1.61 0.83 1.52 0.78 2.00 0.83 1.98 0.86 1.95 0.87 1.88 0.86 1.77 0.81...
  • Page 14: Fan Performance

    5. Fan performance 5-1. Air velocity distributions ¢ Models: ASEH07KLTA and ASEH09KLTA Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up...
  • Page 15 ¢ Model: ASEH12KLTA Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view Horizontal louver: Down...
  • Page 16: Airflow

    5-2. Airflow ¢ Model: ASEH07KLTA  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 12 - 5-2. Airflow 5. Fan performance...
  • Page 17 ¢ Model: ASEH09KLTA  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 13 - 5-2. Airflow 5. Fan performance...
  • Page 18 ¢ Model: ASEH12KLTA  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 14 - 5-2. Airflow 5. Fan performance...
  • Page 19: Operation Noise (Sound Pressure)

    6. Operation noise (sound pressure) 6-1. Noise level curve ¢ Model: ASEH07KLTA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET 1,000...
  • Page 20: Sound Level Check Point

    ¢ Model: ASEH12KLTA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 21: Safety Devices

    7. Safety devices Model Type of Protection form protection ASEH07KLTA ASEH09KLTA ASEH12KLTA Circuit protection Current fuse (PCB*) 250 V, 3.15 A More than 80°C Activate Fan motor speed down Fan motor Thermistor protection protection 80°C or less Reset Fan motor speed recover *PCB: Printed Circuit Board - 17 - 7.
  • Page 22: Remote Controller

    8. Remote controller 8-1. Wireless remote controller ¢ Overview a MODE button • Switches operation mode (AUTO, COOL, DRY, FAN, and HEAT). • Starts/ends the remote controller custom code (max. 4 types) change. b FAN SPEED button c POWERFUL button d ECONOMY button e CANCEL button f SLEEP TIMER button...
  • Page 23 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 162 × 45 × 18 Weight 65.5 (without batteries)  Holder Unit: mm Top view Ø 3.9 (Hole) Hole 26.6 49.3 Front view Side view Size (H ×...
  • Page 24: Function Settings

    9. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 9-1. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting proce- dure and the content of each function setting, select appropriate functions for your installation envi- ronment.
  • Page 25 STEP 2: Selecting the function number and setting value 1. Press the TEMP./SELECT ( ) buttons to select the function Function number number. To switch between the left and right digits, press the MODE button. 2. Press the FAN SPEED button to proceed the setting value. To re- turn the function number selection, press the FAN SPEED button again.
  • Page 26 ¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected.  Function setting list Function no. Functions Filter sign 30/31...
  • Page 27 2) Room temperature control for indoor unit sensor Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature of the room temperature sensor is corrected as follows: Corrected temp.
  • Page 28 5) Indoor unit fan control for energy saving for cooling Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation. Function number Setting value Setting description Factory setting Disable Enable ♦...
  • Page 29: Custom Code Setting For Wireless Remote Controller

    9-2. Custom code setting for wireless remote controller To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code.
  • Page 30: Accessories

    10. Accessories 10-1. Models: ASEH07KLTA, ASEH09KLTA, and ASEH12KLTA Part name Exterior Part name Exterior Self-tapping screw Operation manual (Large) Operation manual Self-tapping screw (CD-ROM) (Small) Installation manual Wall hook bracket Remote controller Battery Remote controller holder - 26 - 10-1. Models: ASEH07KLTA, ASEH09KLTA, and ASEH12KLTA 10.
  • Page 31: Optional Parts

    11. Optional parts 11-1. Others Exterior Part name Model name Summary Air Cleaning Air Cleaning Filter can be mounted to UTR-FA16-5 Filter the indoor unit. Remotely manage an air conditioning system using mobile devices such as smartphones and tablets. UTY-TFSXF2 Appropriate application for each region WLAN Adapter is required to use this option.
  • Page 32 WALL MOUNTED ASEH07–12KLTA WALL MOUNTED ASEH07–12KLTA...
  • Page 33: Part 2. Outdoor Unit

    Part 2. OUTDOOR UNIT SINGLE TYPE: AOEH07KLTA AOEH09KLTA AOEH12KLTA...
  • Page 34: Specifications

    1. Specifications Type Inverter, Heat pump Model name AOEH07KLTA AOEH09KLTA AOEH12KLTA Power supply 230 V~ 50 Hz Power supply intake Outdoor unit Available voltage range 198—264 V Starting current Cooling 1,650 1,700 Airflow rate Heating 1,450 1,470 Type × Qty Propeller fan ×...
  • Page 35 OUTDOOR UNIT AOEH07–12KLTA OUTDOOR UNIT AOEH07–12KLTA...
  • Page 36: Dimensions

    2. Dimensions 2-1. Models: AOEH07KLTA, AOEH09KLTA, and AOEH12KLTA Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 32 - 2-1. Models: AOEH07KLTA, AOEH09KLTA, and AOEH12KLTA 2.
  • Page 37: Installation Space

    3. Installation space 3-1. Models: AOEH07KLTA, AOEH09KLTA, and AOEH12KLTA ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
  • Page 38  Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
  • Page 39  Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
  • Page 40: Refrigerant Circuit

    4. Refrigerant circuit 4-1. Models: AOEH07KLTA, AOEH09KLTA, and AOEH12KLTA Heat exchanger 3-way 2-way (INDOOR) valve valve Muffler Muffler 4-way valve Strainer Expansion valve Heat exchanger Strainer (OUTDOOR) Cooling Heating : Thermistor (Discharge temperature) : Thermistor (Heat exchanger middle temperature) : Thermistor (Outdoor temperature) : Thermistor (Heat exchanger out temperature) : Thermistor (Pipe temperature) : Thermistor (Room temperature)
  • Page 41: Wiring Diagrams

    5. Wiring diagrams 5-1. Models: AOEH07KLTA, AOEH09KLTA, and AOEH12KLTA - 37 - 5-1. Models: AOEH07KLTA, AOEH09KLTA, and AOEH12KLTA 5. Wiring diagrams...
  • Page 42: Capacity Compensation Rate For Pipe Length And Height Difference

    6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Models: AOEH07KLTA and AOEH09KLTA NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 43: Model: Aoeh12Klta

    6-2. Model: AOEH12KLTA NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length (m) COOLING — — — 0.858 0.868 — — 0.929 0.872 0.882 Indoor unit is higher than outdoor unit *1 — 0.960 0.933 0.876 0.885...
  • Page 44: Additional Charge Calculation

    7. Additional charge calculation 7-1. Models: AOEH07KLTA and AOEH09KLTA Refrigerant type Factory charge amount ¢ Refrigerant charge Total pipe length 15 or less 20 (Max.) 20 g/m Additional charge amount 7-2. Model: AOEH12KLTA Refrigerant type Factory charge amount ¢ Refrigerant charge Total pipe length 15 or less 20 (Max.)
  • Page 45: Airflow

    8. Airflow 8-1. Model: AOEH07KLTA  Cooling 1,650  Heating 1,450 8-2. Model: AOEH09KLTA  Cooling 1,650  Heating 1,450 8-3. Model: AOEH12KLTA  Cooling 1,700 1,001  Heating 1,470 - 41 - 8-1. Model: AOEH07KLTA 8. Airflow...
  • Page 46: Operation Noise (Sound Pressure)

    9. Operation noise (sound pressure) 9-1. Noise level curve ¢ AOEH07KLTA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 47: Sound Level Check Point

    ¢ AOEH12KLTA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz 9-2.
  • Page 48: Electrical Characteristics

    10. Electrical characteristics Model name AOEH07KLTA AOEH09KLTA AOEH12KLTA Voltage Power supply Frequency Max operating current* Starting current Circuit breaker current Power cable Wiring Cross-sectional spec.* Connection area cable* Limited wiring length NOTES: • *1: Maximum operating current is the total current of the indoor unit and the outdoor unit. •...
  • Page 49: Safety Devices

    11. Safety devices Model Type of Protection form protection AOEH07KLTA AOEH09KLTA AOEH12KLTA Circuit Current fuse (PCB*) 250 V, 20 A protection 85—122°C Activate Fan motor stop Fan motor Thermal protection program protection 77—114°C Reset Fan motor restart 110 °C Activate Compressor stop Terminal protection program (Discharge temp.)
  • Page 50: Accessories

    12. Accessories 12-1. Models: AOEH07KLTA, AOEH09KLTA, and AOEH12KLTA Part name Exterior Part name Exterior Drain pipe - 46 - 12-1. Models: AOEH07KLTA, AOEH09KLTA, and AOEH12KLTA 12. Accessories...