Summary of Contents for Fujitsu AIRSTAGE AUXB004GLEH
Page 1
INSTALLATION MANUAL INDOOR UNIT (Cassette Type) For authorized service personnel only. INSTALLATIONSANLEITUNG INNENGERÄT (Kassettentyp) Nur für autorisiertes Fachpersonal. MANUEL D’INSTALLATION UNITÉ INTÉRIEURE (type cassette) AUXB004GLEH Pour le personnel agréé uniquement. AUXB007GLEH MANUAL DE INSTALACIÓN AUXB009GLEH AUXB012GLEH UNIDAD INTERIOR (Tipo casete) AUXB014GLEH Únicamente para personal de servicio autorizado.
INSTALLATION MANUAL This mark indicates procedures which, if improperly performed, CAUTION might possibly result in personal harm to the user, or damage PART No. 9371022635 to property. VRF system indoor unit (Cassette type) Read carefully all security information before use or install the air conditioner. Contents Do not attempt to install the air conditioner or a part of the air conditioner by yourself.
Do not discard any accessories needed for installation until the installation work has been Description Model Application completed. Fresh air intake kit UTZ-VXAA To take fresh air. Name and Shape Q’ty Application Wireless LAN adapter UTY-TFSXZ* For wireless LAN control. Operating manual Supply power to the indoor unit PCB when External power supply...
H: Maximum height from floor to ceiling Fig. D Drain pipe (O.D. ø25.4) Unit: mm H (mm) Model name AUXB004 AUXB007 AUXB009 AUXB012 AUXB014 AUXB018 AUXB024 Standard mode 2,700 2,700 2,700 2,700 2,700 2,700 2,700 High Ceiling 3,000 3,000 3,000 3,000 mode * Be sure to make the function settings with the remote controller according to the...
4.3.3. Pipe connection 4.2. Pipe requirement When the flare nut is tightened properly by Tighten with 2 your hand, hold the body side coupling with CAUTION wrenches. a separate spanner, then tighten with a torque wrench. (See the table below for the Holding Refer to the installation manual for the outdoor unit for description of allowable pipe flare nut tightening torques.)
When lifting up drain: NOTE: Check for drainage Drain pipe • Height of inclined pipe should be less than 700 mm from the ceiling. A rise dimension Pour about 1 liter of water over this range will cause leakage. from the position shown in the •...
Breaker should be installed at every refrigerant system. Do not use a breaker in a different 6.3. Unit wiring refrigerant system. Refer to the table for the breaker specifications of each installation condition. Perform the power crossover wiring within the range of the same refrigerant system. When the Before attaching the cable to terminal block.
6.3.2. Transmission and Remote controller cable (2) Connect the connection cable, with the cable tie. Transmission cable Remote controller cable Y1,Y2: Remote 30 mm 30 mm controller cable Shield cable Cable tie (Medium) (no film) (Accessories) 40 mm X1, X2: •...
6.5.3. Connection methods DC power supply Wire modification for External IMPORTANT: P.C.B 12 to 24V input/output wire Be sure to insulate the connection between the Load resis- (1) Remove insulation from wire at- tance wires. CNA01 tached to wire kit connector. Locally Wire kit connector (2) Remove insulation from field...
● When function setting is “Emergency stop” mode. Operation behavior [In the case of “Edge” input] Connector Output voltage Status Connector Input signal Command Stop External output1 OFF → ON Emergency stop Pins 1-2 DC 12 V Operation Ch1 of CNA01 or CNA02 ON →...
Function 7.2. Custom code setting Function Setting number Default Details number • Selecting the custom code prevents the indoor unit mix-up. (figure below) (Up to 4 codes Allow an external controller to start 00 Start/Stop can be set.) or stop the system, or to perform an Emergency •...
7.3.2. Checking the function settings (2) Open the intake grille and remove. Press and hold the “MANUAL AUTO” button on the indoor unit for 3 seconds to check the function settings. It is necessary to disconnect the power in order to return to normal operation mode.
8.3. Attach the intake grille 11. ERROR CODES The installation is the reverse of “REMOVING THE INTAKE GRILLE”. If you use a wired type remote controller, error codes will appear on the remote controller The intake grille can be rotated and installed 4 ways to suit the user’s preference. display.