@ 1”±0.2“ WC Approx. SPDT/ (250 Pa ± 50 Pa) 0574 (12.5 Pa to 250 Pa) Auto Reset 0.06" to 0.6” WC (15 Pa to 150 Pa) Setpoint accuracy tolerance and switching differential decrease proportional to setpoint decrease. Siemens Industry, Inc.
Installation Mount the unit with the diaphragm in any vertical plane. Connect the static pressure line(s) as shown in Figure 1. Switch Nut & Integral Ferrule Tubing Figure 1. Connecting the Static Pressure Line. Page 2 Siemens Industry, Inc.
Page 3
2. Adjust the setpoint until switching occurs at the required point. 3. Check the setpoint for accuracy with a magnahelic gauge. The Red Band Is " The Setpoint Location On The Scale 12.0 Figure 3. Adjusting the Setpoint. Siemens Industry, Inc. Page 3...
Figure 5. Manual Reset Switch 141-0575. Figure 6. Auto Reset Switches 141-0518 and 141-0574. SPDT terminals are marked Common (C), Normally Open (NO), and Normally Closed (NC). Figure 7. Auto Reset Switches to Prove Excessive Airflow or Pressure. Page 4 Siemens Industry, Inc.
Page 5
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Powers is a registered trademark of Siemens Industry, Inc. Other product or company names mentioned herein may be the trademarks of their respective owners.