FEATURES MODEL ABG18LVTB / AOG18LALL ABG24LVTA / AOG24LALA FEATURES Energy efficiency class MODEL ABG18LVTB ABG24LVTA Cooling Heating Flexible installation Example for floor installation Example for ceiling installation Easy installation Main work settings can be done easily from the remote controller at installation Main work settings Setting by wireless or wired remote controller...
Page 5
10°C HEAT Operation *Only available with Wireless RC. The room temperature can be set to go no lower than 10°C, thus ensuring that the room does not get too cold when not occupied Caution) • When the room temperature is higher than 10°C, “10°C HEAT” operation will not start. Operation starts and maintains the room temperature at 10°C when the temperature drops below 10°C.
WIRELESS REMOTE CONTROLLER FEATURES 4 mode timer setup available (ON / OFF / PROGRAM / SLEEP). ¾ Easy operation. ¾ Easy to change signal code (max. 4 units) by button operation. ¾ Simple function setting ...
Page 7
FUNCTIONS MODE button Selects the operating mode (AUTO, COOL, DRY, FAN, HEAT). /Start / end R.C. signal code change. (Max 4 types) 10°C HEAT button SET TEMP. button ( ▲ / ▼ ) Sets the indoor temp./ Sets R.C. signal code. ECONOMY button SLEEP button Pressed to select sleep timer.
SPECIFICATIONS FLOOR / CEILING MODEL Type INVERTER HEATPUMP Model name AB¾G18LVTB AB¾G24LVTA Power source 230V ~ 50Hz Available voltage range 198 - 264V ~ 50Hz 5.20 6.80 Rated Btu/h 17700 23200 Cooling 0.90 - 5.90 0.90 - 8.00 Min - Max Btu/h 3100 - 20100 3100 - 27300...
Page 9
Model name AB¾G18LVTB AB¾G24LVTA Cooling Energy efficiency class Heating (Average) Cooling 5.2 (35˚C) 6.8 (35˚C) Pdesign Heating (Average) 5.2 (-10˚C) 6.0 (-10˚C) SEER Cooling 6.10 5.60 kWh/kWh SCOP Heating (Average) 4.00 3.90 Annual energy consumption kWh/a QHE (Average) 1819 2150 Cooling Sound power level High...
DIMENSIONS MODEL : ABG18LVTB, ABG24LVTA (Unit : mm) Rear view Side view (Drain hose) Bottom view When installing set to wall install the accessory wall bracket at the position as shown in the fi gure, and mount the set to it. Wall bracket Side of set ø100...
Page 11
INSTALLATION PLACE (Unit : mm) Floor type Left Right 300 or more 300 or more Ceiling type Ceiling Left Right Indoor unit 150 or more 300 or more Ceiling 20 or more Obstruction Floor - (01 - 08) -...
FAN PERFORMANCE 7-1. AIR VELOCITY DISTRIBUTION Conditions MODEL : ABG18LVTB (UNDER CEILING) Fan speed : High Operation mode : Fan Unit : (m/s) 0.25 Top view Vertical flap : Up Horizontal flap : Center Unit : (m/s) 0.25 Top view Vertical flap : Up Horizontal flap : Right &...
Page 16
Conditions MODEL : AB ¾ G18LVTB (FLOOR CONSOLE) Fan speed : High Operation mode : Fan Unit : (m/s) 0.25 Top view Vertical flap : Down Horizontal flap : Center Unit : (m/s) 0.25 Top view Vertical flap : Down Horizontal flap : Right &...
Page 17
Conditions MODEL : AB ¾ G24LVTA (UNDER CEILING) Fan speed : High Operation mode : Fan Unit : (m/s) 0.25 Top view Vertical flap : Up Horizontal flap : Center Unit : (m/s) 0.25 Top view Vertical flap : Up Horizontal flap : Right &...
Page 18
Conditions MODEL : AB ¾ G24LVTA (FLOOR CONSOLE) Fan speed : High Operation mode : Fan Unit : (m/s) 0.25 Top view Vertical flap : Down Horizontal flap : Center Unit : (m/s) 0.25 Top view Vertical flap : Down Horizontal flap : Right &...
7-2. AIRFLOW MODEL : ABG18LVTB Cooling Number of Fan speed rotations Airflow (r.p.m.) HIGH 1040 QUIET Heating Number of Fan speed rotations Airflow (r.p.m.) HIGH 1040 QUIET - (01 - 16) -...
Page 20
MODEL : ABG24LVTA Cooling Number of Fan speed rotations Airflow (r.p.m.) HIGH 1330 1150 1000 QUIET Heating Number of Fan speed rotations Airflow (r.p.m.) HIGH 1300 1150 1000 QUIET - (01 - 17) -...
ELECTRIC CHARACTERISTICS Model name AB ¾ G18LVTB AB ¾ G24LVTA Voltage 230 ~ Power supply Frequency Max. operating current 0.45 0.70 Connection cable *1) Wiring Spec. Limited wiring length *1) Wiring Spec. Selected Sample (Selected based on Japan Electrotechnical Standards and Codes Committee E0005) - (01 - 20) -...
SAFETY DEVICES Model Protection form AB ¾ G18LVTB AB ¾ G24LVTA Circuit protection Current fuse (PCB) 250V 3.15A 135 ± 15 °C OFF Thermal protection Fan motor protection program 115 ± 15 °C ON - (01 - 21) -...
EXTERNAL INPUT & OUTPUT Connector INPUT OUTPUT REMARKS See external CN102 Control input — input/output settings for CN103 — Operation status output details. 11-1. EXTERNAL INPUT CONTROL INPUT (Operation/Stop or Forced stop) The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop"...
11-2. EXTERNAL OUTPUT OPERATION STATUS OUTPUT An air conditioner operation status signal can be output. Circuit diagram example Indoor Connected unit control PC board Connector Ex.)Relay unit Ex.)Display 24V DC Relay power supply *10 m Signal Field supply * Make the distance from the PC board to the connected unit within 10m.
FUNCTION SETTINGS 12-1. INDOOR UNIT INDOOR UNIT DIP SW Remote controller address setting Jumper Wire Setting forbidden SWITCH POSITION MAIN PCB Indoor unit Printed circuit board DIP-SW SETTING Remote controller address setting A number of indoor units can be operated at the same time using a wired remote controller. Set the unit number of each indoor unit using the DIP switches on the indoor unit circuit board.
12-2. INDOOR UNIT (Setting by remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit to malfunction. • After the power is turned on, perform The Function Setting according to the installation conditions using the remote controller.
Page 29
CONTENTS OF FUNCTION SETTING • Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in accordance with the installed condition. After the power is turned on, perform the Function Setting on the remote control. •...
Page 30
4) Heater room temperature correction Depending on the installed environment, the room temperature sensor may require correction. The settings may be changed as shown in the table below. ( . . .Factory setting) Setting Description Function Number Setting Value Standard ...
Page 31
REMOTE CONTROLLER SIGNAL CODE SETTING Use the following steps to select the signal code of the remote controller. (Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.) 1.
OPTIONAL PARTS 13-1. CONTROLLER Exterior Parts name Model No. Summary Large and full-dot liquid Wired remote crystal screen, wide and UTY-RVN ¾ M controller large keys easy to press, user-intuitive arrow key. The room temperature can Wired remote be controlled by detecting the UTY-RNN ¾...
Page 33
2. OUTDOOR UNIT SINGLE TYPE : AOG12LALL AOG14LALL AOG18LALL AOG24LALA DTR_AO099E_02 2013.02.28...
SPECIFICATIONS Type INVERTER HEAT PUMP Model name AO G12LALL AO G14LALL AO G18LALL AO G24LALA Power source 230V ~ 50Hz Available voltage range 198 - 264V ~ 50Hz Starting current Cooling 1780 1910 2000 2470 Airflow rate Heating 1630 1740...
DIMENSIONS MODEL : AOG12LALL, AOG14LALL, AOG18LALL, AOG24LALA (Unit : mm) Top view Front view AO G12LALL AO G24LALA AO G14LALL AO G18LALL Air flow Side view Bottom view INSTALLATION PLACE When there are obstacles at When there are obstacles at When there are obstacles at the the back or front sides.
CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE This table is created using the maximum capacity. MODEL : AOG12LALL Pipe length (m) COOLING 0.903 0.894 0.867 Û 1 0.964 0.918 0.909 0.881 Indoor unit is higher than 0.988 0.968 0.922...
Page 41
This table is created using the maximum capacity. MODEL : AOG14LALL Pipe length (m) COOLING 0.953 0.950 0.947 Û 1 0.983 0.968 0.966 0.962 Indoor unit is higher than 0.988 0.987 0.972 0.970 0.966 outdoor unit. 0.992 0.992 0.991 0.976 0.974...
Page 42
This table is created using the maximum capacity. MODEL : AOG18LALL Pipe length (m) COOLING 0.953 0.950 0.947 Û 1 0.983 0.968 0.966 0.962 Indoor unit is higher than 0.988 0.987 0.972 0.970 0.966 outdoor unit. 0.992 0.992 0.991 0.976 0.974...
Page 43
This table is created using the maximum capacity. MODEL : AOG24LALA Pipe length (m) COOLING 0.963 0.961 0.959 Û 1 0.984 0.981 0.979 0.977 0.975 Indoor unit is higher than 0.988 0.988 0.985 0.983 0.981 0.979 outdoor unit. 0.992 0.992 0.992...
AIRFLOW MODEL : AOG12LALL Cooling Number of rotations Airflow (r.p.m.) 1780 1048 Heating Number of rotations Airflow (r.p.m.) 1630 MODEL : AOG14LALL Cooling Number of rotations Airflow (r.p.m.) 1910 1124 Heating Number of rotations Airflow (r.p.m.)
Page 46
MODEL : AOG18LALL Cooling Number of rotations Airflow (r.p.m.) 2000 1177 Heating Number of rotations Airflow (r.p.m.) 1910 1124 MODEL : AOG24LALA Cooling Number of rotations Airflow (r.p.m.) 2470 1050 1454 Heating Number of rotations Airflow...
ELECTRIC CHARACTERISTICS Model name AOG12LALL AOG14LALL AOG18LALL AOG24LALA Voltage 230 ~ Power supply Frequency *1) Max operating current 10.0 12.5 13.5 Starting Current Main Fuse (Circuit breaker) *2) Wiring Spec.: Current Power Cable *1) The maximum current is the total current of indoor unit and outdoor unit. *2) Wiring Spec.: Selected Sample (Selected based on Japan Electrotechnical Standards and Codes Committee E0005)
SAFETY DEVICES Model Protection form AO G12LALL AO G14LALL AO G18LALL AO G24LALA 250V 20A Current fuse (Near the terminal) 250V 5A Circuit protection Current fuse 250V 15A (Main printed 250V 3.15A circuit board) Fan motor Thermal protection OFF : 100 °C...